Optical smoke detector FSS-001
Mua ngay Gọi điện xác nhận và giao hàng tận nơiDescription
PRODUCT DESCRIPTION
- The FSS-001 is an optical smoke detector for early fire warning.
- It responds to a fixed smoke concentration threshold.
- It works with the FCP and FSP conventional control panels.
The optical smoke fire detector gives reliable early warning of a fire. It responds to a fixed smoke concentration threshold in the protected premises.
The smoke sensitivity is factory preset to European Standard ISO 7240 / TCVN 7568-14:2025-7.
A microprocessor controls the detector. FSS operates with an improved algorithm. The algorithm compensates for contamination of the optic chamber. It signals when the chamber needs dusting. Cleaning is quick because the body cover is easy to dismantle and assemble.
The optic chamber and the new screen technology give high protection against dust particles and insects. The detector also works under strong air flow.
Technical data
| Parameter | Value |
|---|---|
| Supply voltage | (10-30)VDC |
| Duty mode current | 120 μA |
| Fire condition current | (18-55) mA |
| Terminals | For wires with cross section (0.8-2.5)mm2 |
| Degree of protection | IP 43 |
| Operation temperature | Minus 10oC to 55oC |
| Relative humidity | (93±3) % at 40oC |
| Sensitivity | In accordance with ISO 7240 / TCVN 7568-14:2025-7 |
| Mounting | Using bases of series 8000 |
| Dimensions (base included) | Ø100, h 47 mm |
| Casing material | ABS plastics, white |
| Weight (base included) | 0.100 kg |
| Protected area | Circle with diameter 15m, h 11m |
Pairing the FSS-001 with a control panel
The FSS-001 is designed for FireSmart’s conventional (zone-based) control panels, the FCP and FSP series. Each zone supports up to 32 detectors on an electronically supervised circuit.
Some buildings need a wireless installation with no cabling. This is common in renovations and heritage buildings. The equivalent addressable device is the WSD-1 wireless optical smoke detector. It reports to the WCP-1 panel over a self-routing wireless radio mesh instead of signal cabling.
Spacing rules apply to both detector types: see smoke detector spacing per NFPA 72. For climate-specific selection notes, read choosing fire detectors for hot, humid climates.
Frequently asked questions about the Optical smoke detector FSS-001
What is the Optical smoke detector FSS-001 used for?
Optical smoke detector FSS-001 is a component of the FireSmart fire alarm system.
Which standard does it meet?
It is designed to meet TCVN 7568-14:2025 (based on ISO 7240), the Vietnamese standard for the design and installation of fire alarm systems.
How can I get a quote or technical support?
Contact FireSmart — a Vietnamese manufacturer of fire alarm devices and systems — for consultation and pricing.