Fire alarm sounder and strobe FSBL-001
Mua ngay Gọi điện xác nhận và giao hàng tận nơiDescription
The FSBL-001 combines a fire alarm sounder and a strobe indicator light to warn occupants of a fire condition with both sound and light.
Mounting and placement
The FSBL-001 is designed for wall mounting in corridors, stairwells and escape routes. Mount at a minimum height of 2.0 m from the finished floor to the device, with units spaced so the red strobe flash stays synchronized (typically ≤ 45 m between units on the same circuit). The sounder reaches up to 90 dB at 1 m on 24 VDC. Per TCVN 7568-3:2015, the audible fire alarm signal must exceed the ambient noise level by at least 10 dBA (within a 65–105 dBA range), with a minimum of 75 dBA in areas where occupants may be sleeping.
Key features
- Combined audible and visual alarm
- High-output sounder and red LED strobe
- Compatible with FireSmart control panels
- Simple installation
Standards: designed to meet TCVN 7568-14:2025 (based on ISO 7240); audible output referenced against TCVN 7568-3:2015 sounder requirements. FireSmart does not currently hold EN 54/UL/FM certification for this device.
Compatible with FireSmart conventional fire alarm control panels: FCP. See the full range in the fire alarm systems category.
Frequently asked questions about the FSBL-001
What is the FSBL-001 used for?
It provides combined audible and visual fire alarm warning within a FireSmart system.
Which standard does it meet?
It is designed to meet TCVN 7568-14:2025 (based on ISO 7240).
How can I get a quote?
Contact FireSmart, a Vietnamese manufacturer of fire alarm devices and systems.
Where should the FSBL-001 be mounted?
On a wall in a corridor, stairwell or escape route, at a minimum height of 2.0 m from the finished floor, with units spaced so the strobe flash stays synchronized (typically ≤ 45 m apart).
How loud is the FSBL-001 sounder?
Up to 90 dB at 1 m on 24 VDC. Per TCVN 7568-3:2015, the audible signal must exceed ambient noise by at least 10 dBA (within 65–105 dBA), with a minimum of 75 dBA in sleeping areas.
How is the FSBL-001 checked during routine testing?
During scheduled fire alarm system maintenance, verify the sounder activates and the red strobe flashes in sync when the connected control panel signals an alarm, and visually inspect the lens for damage or discoloration.